Statox 501 HRC and ARE – Detectors for flammable gases

Catalytic sensors detect all flammable substances, but not with the same sensitivity:

For small alkane molecules the HRC sensor is best – for instance methane CH4, ethane C2H6, propane C3H8, or n-butane C4H10.

The measurement of highly volatile liquids (such as fuels or solvents), the ARE sensor is best.

As these sensor heads have no display or relay, they must be operated with the Statox 503 control module. Together they comply with the requirements for functional safety SIL2 level.

Quick navigation:
Technical data | Downloads

Technical data

Sensor: Statox 501 HRC and Statox 501 ARE
Measurable Gases: Combustible Gases
Measurement Range: 0 – 100% LEL
Measurement Principle: Heat of combustion
Detection Limit: 1% LEL
Response Time: t20 < 5 s
Operating Temperature: -20 to +40 °C
Humidity: 0 – 95% RH, non-condensing
Pressure: 700 – 1300 hPa
Power Supply: 3.0 VDC (ARE) / 5.0 VDC (HRC)
Power Consumption: up to 1 W
Connection: 3-wire or 5-wire
Weight: 0.58 kg
Dimensions (HxWxD): 110 x 130 x 60 mm
Material: Aluminium die-cast (painted) or GRP (seawater-resistant variant)
Enclosure Protection Rating: IP54 (Aluminium variant), IP66 (GRP variant)
Ex Protection: EX db eb IIC T6 Gb
Functional Safety: DIN EN 61508 SIL2 (in combination with Statox 503 Control Module)