Technical Data
 Product  Statox 501 IR Transmitter CO2
 Measuring range  0-2 or. 0-5 Vol.%
 Article No.  561708, 561709
 Measuring principle  2-channel NDIR
 Detection limit  0,03 Vol.% CO2
 Repeatability  < ± 2 %
 Display LED  three digit
 Response time  t50 < 15s, t90 < 45s
 Warm up time  20 s, specifications reached after 30 min
 Operating temperature  -20°C to +60°C
 Storage temperature  -20°C to +60°C
 Humidity  0 – 99% r.F.
 Pressure  800 – 1100 hPa
 Power supply  24VDC (18-29VDC)
 Power consumption  1 Watt
 ATEX Approval  EEx de IIC T5
 EMV  According to EN 50270
Statox501IR

Applications:

  • CO2 fertilization
  • Fermentation process
  • Quick freezing
  • Milling
  • Storage / silo inertization
  • Transportion
  • Packaging
  • Extraction
  • Pest control
  • CO2 Cleaning
  • Fire extinguishing